Electrical Engineering

Short-Circuit Current (Ik) Calculation

Estimate the prospective short-circuit current at a given point in the installation, considering transformer impedance and cable impedance.

Units:
in LinkedIn
💡All protection devices (MCBs, fuses, contactors) must have a breaking capacity higher than the prospective short-circuit current Ik at their installation point. Always verify with a full arc-flash hazard assessment for high-power systems.
Ik = U_n / (√3 × Z_total) where Z_total = √(R_total² + X_total²)
ƒ Calculation module
Input
Transformer rating iTransformer apparent power rating in kVA.
kVA
Transformer impedance uk iShort-circuit voltage of the transformer in %. Typically 4–6% for distribution transformers.
%
Secondary voltage (L-L) iTransformer secondary line voltage in Volts.
V
Cable length to fault point iLength of cable from transformer secondary to the fault point (one-way) in metres.
m
Cable cross-section iConductor cross-section of the cable in mm².
mm²
Result
Transformer impedance Z_T [mΩ]
Cable impedance Z_C [mΩ]
Total impedance Z_tot [mΩ]
Short-circuit current Ik [kA]
Minimum breaker breaking capacity [kA]
📊 Global project table — all calculations
No calculations saved yet. Use the table in any formula and click "+ Add row".