Transformer Sizing

Calculate required transformer kVA rating based on connected loads, demand factor and efficiency.

Units:
in LinkedIn
💡Size transformers at 70-80% utilisation for thermal margin and future growth. Demand factor (simultaneity): not all loads run simultaneously. Typical industrial: 0.6-0.8. Inrush current on energisation: 8-12x rated current.
S_kVA = (sum P_loads x demand_factor) / (PF x eta_trafo)
U1 / I1 U2 / I2 S = U x I [kVA] | n = N1/N2 = U1/U2
Input
Total connected load iSum of all connected load nameplate powers in kW.
kW
Demand factor iFraction of loads operating simultaneously. Offices: 0.5-0.7, Production: 0.6-0.85, Lighting: 0.9-1.0.
Average power factor iWeighted average power factor of all loads. Improve with PF correction capacitors.
Transformer efficiency iTransformer efficiency at full load. Distribution transformers: 97-99%.
%
Target utilisation iDesign utilisation of transformer. Recommended: 65-80%.
%
Result
Demand load [kW]
Required transformer kVA [kVA]
Recommended standard size [kVA]
Full load current (400V) [A]
Inrush current (x10) [A]