Electrical Engineering

Minimum Conductor Cross-Section

Calculate the minimum required conductor cross-section to stay within a maximum permissible voltage drop, for 1-phase or 3-phase AC and DC circuits.

Units:
in LinkedIn
💡Always choose the next standard size above the calculated minimum. Standard sizes: 0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 mm². Also verify the selected cable is rated for the current (ampacity).
A_min (1-ph) = 2×ρ×L×I×cos(φ) / ΔU | A_min (3-ph) = √3×ρ×L×I×cos(φ) / ΔU
cross-section A [mm²] Ø U₁ U₂ ΔU
Input
Cable length (one way) iOne-way cable length in metres.
m
Current I iMaximum current through the cable in Ampères.
A
Max. voltage drop ΔU iMaximum permissible voltage drop in Volts. IEC 60364: 3% = 6.9V at 230V (lighting), 5% = 11.5V (motors).
V
Power factor cos φ iPower factor of the load.
System i1-phase AC, 3-phase AC or DC circuit.
Result
Minimum cross-section [mm²]
Recommended standard size [mm²]
Cable resistance (std size) [Ω]
Actual voltage drop (std size) [V]
📊 Global project table — all calculations
No calculations saved yet. Use the table in any formula and click "+ Add row".