Pneumatics
Pneumatic Valve Sizing (Cv/Kv)
Calculate the required Cv/Kv flow coefficient for a pneumatic valve based on required flow, upstream pressure and allowable pressure drop.
Units:
Always size valves 20–30% larger than the calculated minimum Cv. A valve running at 100% Cv is fully open with no control authority. For proportional valves, target 60–80% open at design flow for best control.
Cv = Q / (963 × P1 × √(ΔP/P1)) for subcritical flow (ΔP/P1 < 0.53)
Input
Required flow Q iRequired flow through the valve in normal-litres per minute.
nl/min
Upstream pressure P1 iGauge pressure upstream of the valve in bar.
bar
Downstream pressure P2 iGauge pressure downstream of the valve in bar.
bar
Air temperature iTemperature of the compressed air in °C.
°C
Result
Pressure drop ΔP [bar]
—
P2/P1 ratio
—
Flow type
—
Required Cv
—
Required Kv (m³/h)
—
Recommended minimum Cv (+25%)
—